The concept of virtual synchronous machine (VSM) was proposed to deal with the shortcomings of low inertia and damping of traditional control strategies for power electronic converters. But what if all distributed energy resources and controllable loads in a microgrid adopt the VSM control strategy, and will it present better performance than conventional droop control-based microgrid (DMG)? In this paper, the VSM-based microgrid (VSMG) is analyzed. The small-signal modeling of the VSMG is studied at first. Then static stability and dynamic characteristics of the VSMG are analyzed and compared with the DMG in both frequency-domain and time-domain. With the growing scale of microgrids, their modeling and simulation are becoming significant computational burdens. Inspired by the participation factor analysis of the VSMG and the concept of coherency in power systems, the VSMG small-signal model is equivalent to a modified third-order synchronous generator (SG) model in this paper. The equivalencing involves gray-box system identification and is realized by estimating equivalent electrical parameters alternately and iteratively. The equivalent SG (EqSG) model is compared with three representative model order reduction methods to verify its effectiveness. Simulation results confirm the accuracy of the EqSG model substituting detailed VSMG model in time-domain simulations.
Dynamic Analysis and Model Order Reduction of Virtual Synchronous Machine Based Microgrid
2020-06-01
oai:zenodo.org:7693895
Article (Journal)
Electronic Resource
English
DDC: | 629 |
Virtual Friction: Experimental Validation in a Microgrid of 3 Virtual Synchronous Machines
BASE | 2022
|European Patent Office | 2023
|