Abstract-A new fault phase selection method for transmission lines is proposed in this article. First, fault phase selection factors are constructed based on the relationship between the fault current of each phase and the fault current difference of the other two phases at a relay point. By analyzing different characteristics of fault phase selection factors in the case of different fault types, fault phase selection criteria are proposed. Simulation results show that fast and accurate selection of the fault phase can be achieved within a period cycle after fault occurs. Also, it is verified that the method bears a high sensitivity to all types of faults and is immune to the impact of fault resistance, fault inception angle, fault location, load current, and high-voltage DC lines, which makes it relatively reliable. Even when a developing fault occurs, good selectivity is secure with this method. Furthermore, the method provides sufficient sensitivity for phase selection on the weak-infeed side and parallel lines.


    Access

    Access via TIB

    Check availability in my library

    Order at Subito €


    Export, share and cite



    Title :

    A Novel Fault Phase Selection Scheme Utilizing Fault Phase Selection Factors




    Publication date :

    2015




    Type of media :

    Article (Journal)


    Type of material :

    Print


    Language :

    English



    Classification :

    BKL:    53.33 / 53.33 Elektrische Maschinen und Antriebe






    The selection of test frequencies for system fault diagnosis

    SRIYANANDA, H. / TOWILL, D. / WILLIAMS, J. | AIAA | 1973


    Fault tolerant power distribution in vehicle with power selection

    YU WANGLIN / PARKINSON JOHN | European Patent Office | 2022

    Free access