It is the consensus of the Design Review Team that the standby diesel generator should function as intended, and in doing so, should meet the needs of the (SNF) CVDF Project. The major comments received from the Design Review Team which require action are as follows: (1) the deletion of the requirement to heat trace the piping from the diesel storage tank to the diesel day tank and to heat the diesel storage tank; removing the requirement to heat trace the sprinkler piping in the process bays and (2) the relocation of the Diesel Generator Building away from the railroad tracks. The design drawings, DRD, and the FSAR will require revisions to incorporate these changes.