The original Coupled Leakage Model of a multiple winding transformer embodies the subject magnetic circuit by magnetically coupling the secondary referenced leakage inductances. Leakage inductance is included in each of the multiple secondary windings, however this model introduced an effective coupling coefficient between the leakages. The model is further extended here to show that it fully supports alternate forms whereby the leakage inductance can be reflected in part, or in total, into the primary winding. Experimental and circuit simulation results are included to verify these alternate forms of the model. Lastly, a two winding version of the Coupled Leakage Model is compared to an existing two winding model in order to illustrate other differences.


    Access

    Check access

    Check availability in my library

    Order at Subito €


    Export, share and cite



    Title :

    Alternate forms of the Coupled Leakage Model


    Contributors:


    Publication date :

    2013-03-01


    Size :

    2551542 byte





    Type of media :

    Conference paper


    Type of material :

    Electronic Resource


    Language :

    English