Design considerations of and field tests at Philip Sporn Station with first 2-cycle breaker for transmission line voltages; breaker interrupted transmission line and bus faults while mounted on trailer on which it was shipped; maximum breaker duty was 10,230 mva, which is believed to be highest fault duty ever imposed on 138-kv breaker in field test; longest interrupting time was 1.85 cycles. (see also Elec Eng v 81 n 6, 7 June 1962 p 445-50, July p 505-7)
2-cycle 138-Kv 10,000,000-Kva air-blast circuit breaker
AIEE -- Trans
AIEE -- Transactions ; 81 , n 64, Part 3
1963
15 pages
Article (Journal)
English