Analysis the efficiency for the use of motors that place in Geothermal Powerplant #2, by implementing automated system for the control of 's speed mode so that the financial and non-financial benefits can be obtained. Automation system in controlling the cooling tower fan speed mode in order to adjust conditions in the safe category, so that power efficiency can be applied continuously by minimizing decision errors or negligence in operation. The analysis based on the operation characteristics, the design of the generation plant, heat balance modeling simulation, and the related laws of physics and mathematical equations. By considering the reliability of the generation powerplant. Obtained a change in the operating pattern of the cooling tower fan from initially operating entirely in high speed mode (5H0L) to 4 fans in high speed mode and 1 fan in low speed mode (4H1L), with the power efficiency obtained from the success of the change amounting to 58.72 kW.


    Access

    Download


    Export, share and cite



    Title :

    Analisis Efisiensi Daya pada Otomatisasi Sistem Kendali Kecepatan Fan Cooling Tower Unit PLTP #2


    Contributors:

    Publication date :

    2019-12-05


    Remarks:

    doi:10.30998/string.v4i2.5348
    STRING (Satuan Tulisan Riset dan Inovasi Teknologi); Vol 4, No 2 (2019); 186-195 ; 2549-2837 ; 2527-9661



    Type of media :

    Article (Journal)


    Type of material :

    Electronic Resource


    Language :

    English



    Classification :

    DDC:    629