Abstract A novel fault line section locating method of non-solidly grounded system based on Prony relative entropy theory was proposed in this paper. Firstly, piecewise Prony algorithm was used to fit the transient zero-sequence current signal of each detection point in the first T/20 cycle after fault occurs; secondly, transient zero-sequence dominant components were extracted and the relative entropy values of adjacent detection points were computed; lastly, the fault section was located by use of the feature that the transient zero-sequence currents from the same side of fault point possess high similarity while the opposite side of fault point possess low similarity. Simulation results verify the validity and accuracy of the method in this paper.
A Novel Method of Fault Section Locating Based on Prony Relative Entropy Theory
01.01.2014
9 pages
Aufsatz/Kapitel (Buch)
Elektronische Ressource
Englisch
A Novel Method of Fault Section Locating Based on Prony Relative Entropy Theory
British Library Conference Proceedings | 2014
|Fault Location on Loop Systems Using the Prony Algorithm
Online Contents | 2006
|A NEW PRONY-BASED CIRCULAR-HYPERBOLIC DECOMPOSITION
Online Contents | 2001
|GROUND-FAULT POSITION LOCATING METHOD AND GROUND-FAULT POSITION LOCATING SYSTEM
Europäisches Patentamt | 2020
|