Generating stations run onto special sidings are employed by Northern States Power Co to feed electricity into local lines when repair work is in progress on substations or transmission lines, and for other emergencies; engine for each unit is 8-cyl, 4-cycle, turbocharged Alco diesel of 12 1/2 in. bore and 13-in. stroke, rated at 1080 hp at 600 rpm; diesel drives 950 kva, 760 kw 3-phase, 60 cycle, 4160/2400 v Elliott generator with 10 kw exciter. (see also similar description in Diesel Progress v 19 n 4 Apr 1953 p 41-3)