Water hammer occurs when the pressure waves are created due to sudden closure of a valve or failure of a pump and continue to move back and forth in the pipeline. This could damage the entire pipe system. The present study describes the simulation of these pressure waves in a pipeline using Bentley Hammer V8i software to model the water pipeline and also to analyse the water hammer effect. In this study, check valve (CV) has been used for the prevention of the surge to the pump. The present numerical simulations establish the location of the valve in the pipeline is to be placed near the pump so as to minimize the effects of the water hammer on the pump.
Optimization of the Location of Check Valve to Minimize the Water Hammer Effects in a Pipeline
Lecture Notes in Civil Engineering
International Conference on Advances in Civil Engineering ; 2020 May 28, 2020 - May 29, 2020
15.12.2021
11 pages
Aufsatz/Kapitel (Buch)
Elektronische Ressource
Englisch
Water pipeline failure due to water hammer effects
Tema Archiv | 2006
|Valve-Induced Water Hammer and Column Separation in a Pipeline Apparatus
Tema Archiv | 2014
|Estimation of water hammer speed in composite pipeline
Tema Archiv | 1998
|