A concept for a miniature, mechanically pumped two-phase cooling loop with high thermal performance was developed. In this feasibility study, a miniature, annular gear pump was inserted into the liquid line of a two-phase LHP-type loop architecture. In contrast to capillary-pumped systems, the functions of liquid pumping and evaporative heat transfer were separated and could be optimized independently. The cooling system was tested in terms of heat transport capability, performance and stability using water as the working fluid. The results show a high heat transfer coefficient of >11 W/(cm2K), a high heat transport capability of >70 W/cm2, and stable working behavior in all orientations. These results were obtained with a device using a simple loop architecture and an evaporator design that was not optimized for this kind of operation.


    Zugriff

    Zugriff prüfen

    Verfügbarkeit in meiner Bibliothek prüfen

    Bestellung bei Subito €


    Exportieren, teilen und zitieren



    Titel :

    A Concept for a Miniature, Mechanically Pumped Two-Phase Cooling Loop


    Weitere Titelangaben:

    Sae Technical Papers


    Beteiligte:
    Schweizer, N. (Autor:in) / Stephan, P. (Autor:in) / Schlitt, R. (Autor:in)

    Kongress:

    International Conference On Environmental Systems ; 2008



    Erscheinungsdatum :

    29.06.2008




    Medientyp :

    Aufsatz (Konferenz)


    Format :

    Print


    Sprache :

    Englisch




    A Concept for a Miniature, Mechanically Pumped Two-Phase Cooling Loop

    Schweizer, N. / Stephan, P. / Schlitt, R. et al. | British Library Conference Proceedings | 2008



    Experimental investigation on a mechanically pumped two-phase cooling loop with dual-evaporator

    Jie, Liu / Nian-Qiang, Pei / Guo, Kai-Hua et al. | Tema Archiv | 2008



    Current Mechanically Pumped Two-Phase Thermal Control Loop Developments

    Delil, A. A. M. / Society of Automotive Engineers | British Library Conference Proceedings | 2004