In this article, novel methods and ideas are introduced, which altogether lead to an accurate model of power transformer windings. First, by the determination of non-dominant (hidden) resonances from frequency-response tests, a ladder model is proposed. Next, it is improved by assigning different values for similar elements of each section of the model. The parameters are obtained by minimizing the error function via a genetic algorithm. Sensitivity analysis is then applied to the obtained model to achieve further examinations and tests. Measurements have been driven from the windings of a 20/0.4-kV, 1600-kVA transformer. Modeling, methodologies, and sensitivity analysis in this article can be very useful for future research aiming to find internal faults of the transformer with the frequency response analysis.
Sensitivity Analysis on Ladder Network Equivalent Circuit Parameters of Power Transformer
Electric power components and systems ; 43 , 19
2015
Aufsatz (Zeitschrift)
Englisch
RC Equivalent Circuit Model Parameters Characterization
SAE Technical Papers | 2020
|Novel equivalent circuit model and statistical analysis in parameters identification
Online Contents | 2003
|Power Quality Assessment through Stochastic Equivalent Circuit Analysis
SAE Technical Papers | 2016
|Analysis for the Double Staggered Ladder Circuit
British Library Online Contents | 1996
|An Estimation Method to Determine Equivalent Circuit Parameters for Harmonic Analysis
Online Contents | 2014
|