The radiation field from the spark discharge on faulty insulators of distribution lines often influences broadcasting services of radio and television, and communication services. The spark discharge occurs due to loose connection in a metal‐fittings connection of strain insulators. The rust of metal‐fittings and the low‐tension of wire are causes of loose connection. In this paper, the generation conditions of spark discharge were clarified by the basic experiment. And the radiation field which includes frequency component of several GHz due to the spark discharge was measured using a 6.6 kV full‐scale distribution line, and the amplitude probability distribution of electric field was analyzed.
Characteristics of Spark Discharge from Faulty Insulators
Electrical engineering in Japan ; 200 , 2
2017
Aufsatz (Zeitschrift)
Englisch
Characteristics of AIN Insulators Spark Plug
British Library Conference Proceedings | 1995
|Ceramic Insulators for Spark Plugs
SAE Technical Papers | 1940
|Spark Discharge Characteristics for Varying Spark Plug Geometries and Gas Compositions
British Library Conference Proceedings | 2022
|Spark Discharge Characteristics for Varying Spark Plug Geometries and Gas Compositions
SAE Technical Papers | 2022
|